6 Setup with the integrated display and adjustment unit

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

When the instrument displays a failure, further information of the

failure is available via the menu item "Diagnosis - Device status".

Furthermore the indication of the input current, the sensor status, the

switch on period and the relay status as well as the input status of the

digital inputs are possible.

The simulation of a measured value is used to check the outputs and

connected components. The simulation can be applied to the percent-

age value, the lin. percentage value and the sensor value.
Note:

Please note that connected system parts (valves, pumps, motors,

control systems) are influenced by the simulation, thus unintentional

plant operating conditions can occur. The simulation is terminated

automatically after approxminately 10 minutes.

Carry out your settings via the appropriate keys and save with

[OK].

Several reset options are available. A reset to basic settings resets

all settings (with a view exceptions) to default. Exceptions are: host

name, IP address, subnet mask, time, language. Further possibilities

are reset of the totalizer as well as the power-on time and relay failure.

The instrument can also be restarted if desired.

The signal conditioning instrument can be locked with a PIN to protect

the set parameters against unauthorized modification. After activa-

tion, it is not possible to carry out a parameter adjustment via the

built-in display and adjustment unit without entering the previously

specified PIN. This locking does not apply to parameter adjustment

with PACTware and the respective DTM.

With every 4 … 20 mA/HART sensor, the measured value can be

transmitted via analog current signal or digital HART signal. This is

regulated via the HART mode or the address. If a HART sensor is set

Diagnostics