5 Connecting to power supply

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

10. For connection of additional relais to terminal strip 3, you have to

proceed as described earlier

The electrical connection is hence finished.
Remember that with Ex applications, the Ex separating wall must be

plugged onto the upper side of the instrument before setup.
Information:

On the active input (terminal 1/2), VEGAMET 391 provides power

for the connected sensors. Power supply and measurement data

are transmitted over the same two-wire cable. This mode is pro-

vided for connection of measuring transducers without separate

operating voltage (sensors in two-wire version).

On the passive input (terminals 5/6), the sensors are not powered

- only the measured value is transmitted. This input is for sensors

with their own, separate operating voltage (sensors in four-wire

version). On a VEGAMET 391 in Ex version, the passive input is

not available due approval-technical reasons.