6 Setup with the integrated display and adjustment unit

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

The prerequisite for this is the support of the HART commands 0, 1,

3, and 15. This information and which measured values are transmit-

ted can be found in the operating instructions manual of the respec-

tive sensor manufacturer.

Carry out your settings via the appropriate keys and save with [OK].

The measured variable defines the applicaton of the measurement

loop, the following settings are available depending on the connected

sensor:

Level

Process pressure

Universal

Temperature

Interface

Flow (only after activating via PACTware or DTM)

Carry out your settings via the appropriate keys and save with [OK].

Through the adjustment the input value of the connected sensor is

converted into a percentage value. This conversion step allows any

input value range to be depicted in a relative range (0 % up to 100 %).
Before carrying out the adjustment, the requested adjustment unit can

be selected. With input selection "Analogue", the adjustment unit is al-

ways "mA". If the HART input is activated, the available unit depends

on the sensor type. With radar, ultrasonic and guided microwave this

is always the distance in metres or feet "m(d)" or "ft(d)", and with pres-

sure transmitters it is e.g. "bar" or "psi".

The following illustrations and examples relate to the min./max. ad-

justment of a radar sensor with HART communication.

1. With

[OK] you prepare the percentage value for editing, with [->]

you place the cursor to the requested position. Set the requested

percentage value with [+] and save with [OK].

2. After entering the percentage value for the min. adjustment, the

suitable distance value must be entered. If you want the use the

Meas. loop - Parameter

Meas. loop - Adjustment