Error code Cause

Rectification

E053

Sensor measuring

range not read cor-

rectly

– Communication error: Check sensor

cable and screening

E062

Pulse priority too

small

– Increase under "Output" the entry

"Pulse output all" so that max. one

pulse per second is outputted.

E110

Relay switching

points too close to-

gether

– Increase the difference between the

two relay switching points

E111

Relay switching

points interchanged

– Change relay switching points for

"On/Off"

E115

Several relays are as-

signef to the pump

control which are not

set to the same fail-

ure mode

– All relays which are assigned to the

pump control must be set to the

same failure mode

E116

Several relays that

are not configured

with the same mode

are assigned to the

pump control

– All relays which are assigned to the

pump control must be set to the

same mode

E117

A monitored pump

signals failure

– Check the faulty pump. For ac-

knowledgement, carry out the reset

"Failure relay 1 … 4" or switch the

instrument OFF and ON again

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

9.3 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our Internet homepage

www.vega.com under: "Downloads - Forms and certificates - Repair

form".
By doing this you help us carry out the repair quickly and without hav-

ing to call back for needed information.

Print and fill out one form per instrument

Clean the instrument and pack it damage-proof

Attach the completed form and, if need be, also a safety data

sheet outside on the packaging

Please ask the agency serving you for the address of your return

shipment. You can find the respective contact data on our website

www.vega.com under: "Company - VEGA worldwide"