11 Supplement

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

Ethernet interface (optional)
Quantity

1 x, cannot be combined with RS232

Data transmission

10/100 MBit

Plug connection

RJ45

Max. cable length

100 m (3937 in)

RS232 interface (optional)
Quantity

1 x, cannot be combined with Ethernet

Plug connection

RJ45 (modem connection cable on 9-pole D-SUB in the

scope of delivery)

Max. cable length

15 m (590 in)

Clock (only with interface option)
Accuracy/Deviation

Ʋ typical

20 ppm (correspond to 10.5 min./year)

Ʋ Max.

63 ppm (correspond to 33 min./year)

Power reserve of the lithium battery (Li/MnO2)

Ʋ typical

10 years at 20 °C

Ʋ Min.

4 years

Indications
Measured value indication

Ʋ graphic-capable LC display

(65 x 32 mm), lighted

digital and quasianalogue indication

Ʋ Max. indicating range

-99999 … 99999

LED displays

Ʋ Status operating voltage

1 x LED green

Ʋ Status fault signal

1 x LED red

Ʋ Status operating relay 1 … 6

6 x LED yellow

Adjustment
Adjustment elements

4 x keys for menu adjustment

PC adjustment

PACTware with respective DTM

Ambient conditions
Ambient temperature

Ʋ Instrument in general

-20 … +60 °C (-4 … +140 °F)

Ʋ USB interface

0 … +60 °C (32 … +140 °F)

Storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Electrical protective measures
Protection rating

Ʋ Front

IP 65

Ʋ Instrument

IP 20

Overvoltage category

II