2 pump control 1/2 (running time controlled) – VEGA VEGAMET 391 4 … 20 mA_HART User Manual

Page 40

Advertising
background image

40

8 Application examples

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

to 5 %, this corresponds to 181 litres. The volume should be displayed

in litres.

Carry out the adjustment in the signal conditioning instrument as

described in chapter "Setup steps". No additional adjustment must

hence be carried out on the sensors. For the max. adjustment, fill the

vessel up to the requested max. level and accept the actually meas-

ured value. If this is not possible, the respective current value can be

entered alternatively. For the min. adjustment, empty the vessel up to

the min. level or enter the respective current value.

To display the percentage level correctly, select under "Measurement

loop - Linearization curve" the entry "Cylindrical tank".

To display the volume in litres, you have to enter "Volume" as unit in

litres under "Measurement loop - Scaling". The allocation is then car-

ried out, in this example 100 % ≙ 10000 litres and 0 % ≙ 0 litres.

Percent is selected as reference value for the relays. The mode of re-

lay 1 is set to overfill protection, relay 2 gets mode dry run protection.

To ensure that the pump switches off in case of failure, the reaction

in case of failure should be adjusted to switching status OFF. The

switching points are adjusted as follows:

Relay 1: Switch-off point 90 %, switch-on point 85 %

Relay 2: Switch-off point 5 %, switch-on point 10 %

Information:

The switch on and off point of the relays must not be adjusted to the

same switching point because this would cause a permanent switchin

on and off when this threshold is reached. To avoid this effect also

with fluctuating product surface, a difference (hysteresis) of 5 % is

useful between the switching points.

8.2 Pump control 1/2 (running time controlled)

Pump control 1/2 is used to control several pumps with the same

function dependent on the previous running time. Always the pump

with the shortest running time is switched on and the pump with

the longest running time switched off. With increased requirement,

all pumps can also run at the same time dependent on the entered

switching points. With this measure, a steady utilization of the pumps

is achieved and the reliability increased.
All relays with activated pump control are not assigned to a certain

switching point but are switched on or off depending on the accu-

mulated operating time. The signal conditioning instrument selects

the relay with the shortest operating time when the switch-on point

is reached and the relay with the longest operating time when the

switch-off point is reached.
Probable failures of the pumps can be processed in addition via the

digital inputs.
With this pump control, there are two different versions:

Adjustment

Linearization

Scaling

Relay

Functional principle

Advertising