VEGA VEGAMET 391 4 … 20 mA_HART User Manual

Page 24

Advertising
background image

24

6 Setup with the integrated display and adjustment unit

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

Carry out your settings via the appropriate keys and save with

[OK].

Scaling means converting the measured value into a certain param-

eter and unit. The linearized percentage value is the source signal

which is used as basis for the scaling. The indication can then show

the volume in litres e.g., instead of the percentage value. Indication

values from max. -99999 to +99999 are possible.

Carry out your settings via the appropriate keys and save with

[OK].

In this menu item you can enter an unambiguous designation for each

measurement loop, e.g. the measurement loop name or the tank or

product designation. In digital systems and in the documentation

of larger plants, a singular designation should be entered for exact

identification of individual measuring points.

Carry out your settings via the appropriate keys and save with

[OK].

Under "Outputs", you'll find the relay/current outputs. With the relay

output, the requested mode ("Overfill protection/Dry run protection" or

"Pump control") must first be selected.

Overfill protection: Relay is switched off when the max. level is

exceeded (safe currentless condition), relay is switched on again

when the level falls below the min. level (switch-on point < switch-

off point)

Dry run protection: Relay is switched off when the level falls

below the min. level (safe currentless condition), relay is switched

on again when the max. level is exceeded (switch-on point >

switch-off point)

Pump control: With several pumps having the same function, the

pumps will be alternately switch on and off according to the adjust-

able criteria

Additional modes such as "Switching window", "Flow" and "Tenden-

cy" can be only adjusted via PACTware and DTM.
Relay 6 can be also configured as fail safe relay. The following exam-

ple shows the adjustment of an overfill protection. Further information

to pump control, tendency recognition or flow measurement are avail-

able in chapter "Application examples".

Meas. loop - Scaling

Meas. loop - Meas. loop

TAG

Meas. loop - Outputs -

Relays outputs