VEGA VEGAMET 391 4 … 20 mA_HART User Manual

Page 25

Advertising
background image

25

6 Setup with the integrated display and adjustment unit

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

Select the requested mode and save with [OK]. By pushing [->], you

reach the next menu item.
1. Now enter the reference value to which the relay switching points

relate. By pushing [->], you reach the next menu item.

2. Now enter the switching points for switching the relay on and off.

In the following window the reaction of the relay in case of failure can

be determined. Here you can define whether, in case of failure, the

switching condition of the relay remains unchanged or the relay is

switched off.

The current output is used to transfer the measured value to a higher

ranking system, for example to a PLC, a control system or a meas-

ured value indication. This is an active output, i.e. a current is provided

actively. The processing unit must hence have a passive current input.
The characteristics of the current output can be set to 0 … 20 mA,

4 … 20 mA or inverted. The reaction in case of failure can also be

adapted to the requirements. The measured variable you refer to can

also be selected.

Carry out your settings via the appropriate keys and save with

[OK].

Meas. loop - Outputs -

Current output