8 Application examples

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

8 Application examples

8.1 Level measurement in a cylindrical tank with

overfill protection/dry run protection

The level is detected via a sensors and transmitted to the signal

conditioning instrument by means of a 4 … 20 mA signal. Here, an

adjustment is carried out converting the input value delivered by the

sensor into a percentage value.
Due to the geometrical form of the cylindrical tank, the vessel volume

does not increase linear with the level. This can be compensated

by selecting the linearization curve integrated in the instrument.

This curve states the relation between percentage level and vessel

volume. If the level should be displayed in litres, also a scaling must

be carried out. For this purpose, the linearized percentage value is

converted into a volume, for example with the unit litres.
Filling and emptying are controlled via relay 1 and 2 which are

integrated in the signal conditioning instrument. During filling, relay

mode "Overfill protection" is set. The relay is thus switched off (safe

currentless condition) when the max. level is exceeded, and switched

on again when the min. level is underrun (switch-on point < switch-off

point). During emptying, mode "Dry run protection" is used. This relay

is thus switched off when the min. level is underrun (safe currentless

condition), and switched on again when the min. level is exceeded

(switch-on point > switch-off point).

Rel. 1

Rel. 2

Rel. 1: 90%

Rel. 2: 5%

100%

0%

Fig. 13: Example for a level measurement, cylindrical tank

A cylindrical tank has a capacity of 10000 litres. The measurement

is carried out with a level sensor operating according to the principle

of the guided microwave. The filling by a tank car is controll via relay

1 and a valve (overfill protection). The discharge is carried out via

a pump and is controlled by relay 2 (dry run protection). The max.

volume should be at 90 % level, these are 9538 litres with a standard

vessel (according to bearing chart). The min. level should be adjusted

Functional principle

Example