11 Supplement

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

Protection class

II

Electrical separating measures
Reliable separation according to VDE 0106 part 1 between power supply, input and digital compo-

nent

Ʋ Reference voltage

250 V

Ʋ Voltage resistance of the isolation

3.75 kV

Galvanic separation between relay output and digital part

Ʋ Reference voltage

250 V

Ʋ Voltage resistance of the isolation

4 kV

Potential separation between Ethernet interface and digital part

Ʋ Reference voltage

50 V

Ʋ Voltage resistance of the isolation

1 kV

Potential separation between RS232 interface and digital part

Ʋ Reference voltage

50 V

Ʋ Voltage resistance of the isolation

50 V

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

11.2 Overview applications/functionality

The following charts provide an overview of the standard applications and functions of signal condi-

tioning instruments VEGAMET 391/624/625 and VEGASCAN 693. They also give information about

whether the respective function can be activated and adjusted via the integrated indicating and

adjustment unit (OP) or via PACTware/DTM.

Application/Function

391

624

625

693

OP

3)

DTM

Level measurement

Process pressure measurement

Differential measurement

-

-

-

Interface measurement

-

-

-

Pressurized vessel

-

-

-

-

Pump control

-

4)

Totalizer

-

-

-

-

Tendency recognition

-

-

Flow measurement

-

-

Simulation sensor value/%-value/lin-%-value

Simulation scaled values

-

Live adjustment

-