8 Application examples

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

again. If the level continues to rise despite operation of a pump, an

additional pump switched on when the level exceeds the 75 % switch-

ing point. And if the level still rises further due to extreme inflow and

exceeds the 90 % limit, pump 3 is also switched on.

Select in the DTM navigation section the menu items "Meas. loop -

Outputs - Relay".

Set mode "Pump control 4" for relays 1 … 3.

Enter the switching points for the affected relays as follows:

– Relay 1 upper switching point = 60.0 %

– Relay 1 lower switching point = 10.0 %

– Relay 2 upper switching point = 75.0 %

– Relay 2 lower switching point = 10.0 %

– Relay 3 upper switching point = 90.0 %

– Relay 3 lower switching point = 10.0 %

The function of pump control 4 is shown in detail in the following dia-

gram. The previously described example is used as a basis.

Rel. 1: 60% On

Rel. 1..3: 10% Off

Rel. 2: 75% On

Rel. 3: 90% On

t(h)

Rel. 3

Rel. no.

Rel. 2

1 2

3

1

2

3

1

2

3 1 2

Rel. 1

Fig. 16: Example of pump control 4

When pump control is activated, the assigned relays and possible

pump malfunctions are also displayed in the measured value indica-

tion.

1 2 3 4 5

Fig. 17: Display indication of a pump control
1 Symbol activated pump control

2 Relay 1 is assigned to the pump control

3 Relay 2 is assigned to the pump control and signals failure

4 Relay 3 is assigned to the pump control

5 Relay 4 is free or not assigned to the pump control