6 Setup with the integrated display and adjustment unit

VEGAMET 391 • 4 … 20 mA/HART

36032-EN-130701

currently measured distance value, select the menu item "Accept"

(live adjustment or adjustment with medium). If the adjustment

should be carried out independent of the measured level, then

select the option "Edit". Enter now the distance value in m [m(d)]

for the empty vessel that is suitable for the percentage value, e.g.

distance from the sensor to the vessel bottom (dry adjustment or

adjustment without medium).

3. Save your settings with [OK] and move to "Max. adjustment" with

[->].

4. As described previously, enter now the percentage value for max.

adjustment and confirm with [OK].

5. After entering the percentage value for the max. adjustment, the

suitable distance value must be entered. If you want the use the

currently measured distance value, select the menu item "Accept"

(live adjustment or adjustment with medium). If the adjustment

should be carried out independent of the measured level, then

select the option "Edit". Enter now the distance value in m [m(d)]

for the full vessel that is suitable for the percentage value (dry

adjustment or adjustment without medium). Keep in mind that the

max. level must be below the radar antenna.

6. Finally save your settings with [OK], the adjustment is finished.

To suppress fluctuations in the measured value display, e.g. caused

by an agitated product surface, an integration time can be set. This

time can be between 0 and 999 seconds. Remember that the reaction

time of the entire measurement will then be longer and the sensor will

react to measured value changes with a delay. In general, a period of

a few seconds is sufficient to smooth the measured value display.

Carry out your settings via the appropriate keys and save with

[OK].

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level, for example, with a cylindrical

or spherical tank. Corresponding linearization curves are prepro-

grammed for these vessels. They represent the correlation between

the level percentage and vessel volume. By activating the appropriate

curve, the volume percentage of the vessel is displayed correctly. If

the volume should not be displayed in percent but e.g. in l or kg, a

scaling can be also set.

Meas. loop - Damping

Meas. loop - Linearization

curve