Lvd1, lvd2, Office alarm relay outputs, Auxiliary battery supply (abs) – GE Industrial Solutions Galaxy Vector Rack Mounted Controller J85501M-1 User Manual

Page 24: Table 2-f: lvd drive terminals

Advertising
background image

Galaxy Rack-Mounted Vector Controller J85501M-1

2 - 10 Product Description

Issue 2 January 2008

LVD1, LVD2

Relay contact outputs for LVD contactor control. Contacts are
rated for 10 amps. Power must be provided externally to the
contactor coil. The contactor coil should have battery
permanently attached. The LVD1 and LVD2 contacts should
complete the circuit to DG. This power is switched by the LVD
control contact closure provided.

Table 2-F: LVD Drive Terminals

Contactor

Name

Alarm Board

Description

LVD1

LVD1-CON1
LVD1-CON2

TB3.6

TB3.7

Dry closure provided. External
power required.

LVD2

LVD2-CON1
LVD2-CON2

TB3.11

TB3.12

Office Alarm Relay

Outputs

All alarm output relays are isolated Form C or transfer type
contacts, consisting of Open (O) and Closed (C) contacts, with a
common Return (R(C)) contact. The de-energized state of the
controller forces these contacts to the alarm state. An alarm
condition results in a closure of the Closed contact to the Return
contact, and an open between the Open and Return contacts.

Table 2-G: BLJ3 Office Alarm Relay Output Terminals

Terminal

Alarm

Alarm Description

C

1

R(C)

1

O

1

ACF

Single AC Fail

TB8.1

TB8.2

TB8.3

BD

Battery on Discharge

TB8.9

TB8.10

TB8.11

HV/2ACF/VLV

2

High Voltage / Multiple
AC Fail / Very Low
Voltage

TB8.5

TB8.6

TB8.7

MJF

Major Fuse

TB7.9

TB7.10

TB7.11

PMJ

Power Major

TB7.1

TB7.2

TB7.3

PMN

Power Minor

TB7.5

TB7.6

TB7.7

1. C: Open contacts. Closed to R(C) when alarm condition exists.

R(C): Return (common)

O: Closed contacts. Open to R(C) when alarm condition exists.

2. Relay assignment is determined by the settings of S1.2 and S1.5:

HV alarm

S1.2-0, S1.5=0

2ACF alarm S1.2=1, S1.5=0

VLV alarm

S1.2=0, S1.5=1

Setting both switches to 1 results in activating HV. The S1.2 setting is only read during
GCM power up.

Auxiliary Battery

Supply (ABS)

Auxiliary Battery Supply (ABS) is connected to the battery
discharge bus and fused through F1 (1-1/3A) for user application
on TB4 pins 1, 3, 5, 9, and 11, and TB5 pin 1. F1 is field
replaceable.