Galaxy Rack-Mounted Vector Controller J85501M-1

Issue 2 January 2008

Installation and Configuration 4 - 7

Batteries

Type

Valve-regulated, flooded

Valve-regulated

Valve-regulated

Battery discharge

test enable

Enabled/Disabled

Disabled

Disabled

High battery

temperature major

alarm

30° to 85°C

55°C

75°C

Battery temperature

compensation

enable

Enabled/Disabled

Disabled

Enabled

High battery

temperature

stepdown voltage

45° to 85°C

75°C

75°C

High battery

temperature voltage

decrease stop

(upper slope limit)

30° to 55°C

45°C

53°C

High battery

temperature voltage

decrease rate (upper

slope per cell)

1 to 5mV/°C

3mV

3mV

Nominal

temperature (no

voltage

compensation)

15° to 30°C

25°C

25°C

Battery low

temperature

compensation

voltage increase

enable

Enabled/Disabled

Disabled

Disabled

Low battery

temperature voltage

decrease stop

(lower slope limit)

-5° to 20°C

0°C

-5°C

Low battery

temperature voltage

decrease rate (lower

slope per cell)

1 to 5mV/°C

3mV

3mV

Battery recharge

current limit enable

Enabled/Disabled

Disabled

Disabled

Battery recharge

current limit

threshold

10-1000A

1000A

1000A

Table 4-A: Configuration Parameters (Continued)

Main Menu

Heading

Parameter

Description

Range

(24V, 48V Systems)

Default (24V, 48V Systems)

Standard

Custom