T1.317 Objects and Attributes Appendix B - 5

Table B-12: Slope Thermal Compensation

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

sc1,stt

State

number

0:disable 1:enable

sc1,rve

Raise voltage enable

number

0:disable 1:enable

sc1,ltt

Lower temperature

number

-5-20:0°C

sc1,ntt

Nominal temperature

number

15-30:25°C

sc1,utt

Upper temperature

number

30-55:45°C

sc1,spt

Step temperature threshold

number

45-85:75°C

sc1,lsp

Lower temperature slope

per cell

number

1-5:3mV/°C

sc1,usp

Upper temperature slope

per cell

number

1-5:3mV/°C

Table B-13: Call-Out

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

p1,phn

Primary phone number

text

Up to 25 characters:“”

a1,phn

Alternate phone number

text

Up to 25 characters:“”

Table B-14: Serial Ports

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

mp1,bdr

Modem baud rate

number

1200,2400,4800,9600, and 19200

mp1,ins

Modem initialization string

text

Up to 25 characters: “at&fev&c1h0

mp1,hsh

Modem handshaking

text

“NO”: none

“SW”: xon and xoff

mp1,nrg

Modem number of rings

before answering

number

1 - 9 rings

lp1,bdr

Local RS-232 baud rate

number

“AUTO”,1200,2400,4800,9600,

and 19200

lp1,hsh

Local RS-232 handshaking

text

“NO”: none
"SW": xon and xoff
"HW": cts and rts