T1.317 Objects and Attributes Appendix B - 3

Table B-5: Rectifiers (xx is 01 to 24)

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

gxx,stt

Individual rectifier state

text

"ON","OFF","STANDBY",

"VACANT"

gxx,adc

Individual rectifier current

number

ddd

Table B-6: Battery Reserve Management

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

br1,cle

Batt recharge current limit

enable

number

0:disable 1:enable

br1,clt

Battery recharge current limit

number

10-1000 A

br1,btc

Battery test class

text

"FLOODED","VALVE-REG"

br1,bte

Battery test enable

number

0:disable 1:enable

br1,btr

Battery test results

mixed

result, reserve, load

code: ok, aborted, failed, not run,

interrupted

reserve: dd.d (hours)

load: dddd (amps)

br1,bts

Battery test state

number

0:inactive 1:active

Table B-7: Battery Sections

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

b01,adc

Battery section 1 current

dddd A

b02,adc

Battery section 2 current

dddd A

Table B-8: Controller Battery Temperature Channels

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

ct1,val

Controller battery temp chan 1

dd °C

ct2,val

Controller battery temp chan 2

dd °C

ct3,val

Controller battery temp chan 3

dd °C

ct4,val

Controller battery temp chan 4

dd °C