Temperature probe alarm is present, Rectifier id conflict alarm is asserted, Converter id (cid) – GE Industrial Solutions Galaxy Vector Rack Mounted Controller J85501M-1 User Manual

Page 67: Alarm, Failure alarm

Advertising
background image

Galaxy Rack-Mounted Vector Controller J85501M-1

Issue 2 January 2008

Troubleshooting 5 - 3

Temperature

Probe Alarm is

present

The Temperature Probe Fail alarm indicates that either there is
something wrong with the temperature connections, or that there
is a problem with one of the external temperature processing
units. An additional possibility is that the alarm is indicating that
the thermal compensation feature is enabled, and that no
temperature probes are present. If there are no temperature
probes connected to the Vector, then disable the Battery Thermal
Compensation Enable setting.

Unexplained

Rectifier Failure

Alarm and

Multiple Rectifier

Failure Alarm

A rectifier that is removed from the plant will generate a
Rectifier Fail Minor alarm. If more than one rectifier is missing,
a Multiple Rectifier Fail Major alarm is generated. To clear these
alarm conditions, go to the Operation Menu and assert the Clear
Events (CLE) command.

Note: A few minutes after executing the Clear Events function
to clear alarms, the controller RFA alarm should clear and no
rectifier should display any alarms. If alarms continue to be
displayed, continue investigating the system for possible
rectifier problems.

Unexplained

Converter Failure

Alarm and

Multiple

Converter Failure

Alarm

A converter that is removed from the plant will generate a
Converter Fail Minor alarm. If more than one converter is
missing, a Multiple Converter Fail Major alarm is generated. To
clear these alarm conditions, go to the Operation Menu and
assert the Clear Events (CLE) command.

Note: A few minutes after executing the Clear Events function
to clear alarms, the controller CFA alarm should clear and no
rectifier should display any alarms. If alarms continue to be
displayed, continue investigating the system for possible
converter problems.

Rectifier Id

conflict alarm is

asserted

This alarm indicates that a rectifier Id has not been set or is
duplicated in the system. Verify all rectifiers are numbered
uniquely between 1 and 24. Refer to numbering procedure in
rectifier manual.

Converter Id

(Cid)

This alarm indicates that a converter Id has not been set or is
duplicated in the system. Verify all converters are numbered
uniquely between 1 and 8. Refer to numbering procedure in bay
manual.