Galaxy Rack-Mounted Vector Controller J85501M-1

4 - 8 Installation and Configuration

Issue 2 January 2008

Contactors

Contactor 1 type

Battery/Load/None

None

Battery

Disconnect voltage,

contactor 1

20-26V, 40-52V

21V, 43.2V

N/A, 43.2V

Reconnect voltage,

contactor 1

20-26V, 40-52V

22.2V, 44.4V

N/A, 44.4V

Contactor 2 type

Battery/Load/None

None

N/A, 43.2V

Disconnect voltage,

contactor 2

20-26V, 40-52V

21V, 43.2V

N/A, 44.4V

Reconnect voltage,

contactor 2

20-26V, 40-52V

22.2V, 44.4V

N/A, 43.2V

Converters

Converter set point

voltage

46-57V

50V

N/A

Converter

shutdown voltage

(disconnect

threshold)

20-26V

21V

N/A

Converter

shutdown voltage

enable (low voltage

disconnect)

Enable/Disable

Disable

N/A

Converter restart

voltage (reconnect

threshold)

20-26V

22.2V

N/A

Boost

Boost feature

enable

Enable/Disable

Disable

Disable

Boost set point
system voltage

24-30V, 48-60V

27.24V, 55.2V

N/A, 55.2V

High boost voltage

major alarm

threshold

26-30V, 52-60V

28.24V, 57V

N/A, 57.0V

High boost voltage

minor alarm

threshold

25-30V, 50-60V

27.74V, 56.2V

N/A, 56.2V

Auto boost feature

enable

Enable/Disable

Disable

Disable

Auto boost duration

(_

× BD duration)

1 to 9

1

N/A, 1

Manual boost

duration

1-250 hours

8

N/A, 8

Boost current limit

(rectifier limit

during boost)

30%-110%

100%

N/A, 100%

Table 4-A: Configuration Parameters (Continued)

Main Menu

Heading

Parameter

Description

Range

(24V, 48V Systems)

Default (24V, 48V Systems)

Standard

Custom