Appendix A - 12 Communications

Issue 2 January 2008

Logging Out of

the Galaxy

Gateway

To terminate the configuration session, enter the “bye”
command. The Galaxy Gateway will notify the user if
configuration is not complete. This message will have the
following format:

NOTICE:

Default gateway may be required for network

access.

Host Name may be required for network access.

Logging off...

Messages referencing the Gateway and Host Name are
acceptable, since these parameters are optional.

Note: If the IP address or Subnet mask messages appear, for
example:

IP Address is required for network access.

Subnet mask is required for network access.

then the configuration procedure must be repeated.

Post Installation

Procedures

Once configuration has been completed

1. Disconnect the serial cable from the Galaxy Gateway (J2

connector).

2. Connect the 9-pin male end of the auxiliary port cable

assembly to the J2 connector on the Galaxy Gateway.

3. Press SW1 (uP reset) on the Galaxy Gateway.

4. After approximately one minute, observe the LEDs on the

Galaxy Gateway.

• Yellow STATUS LED: OFF
• Green STATUS LED: ON
• Link LED: ON
• XMIT/RCV: May be blinking

The Galaxy Gateway should be communicating over the
network.

5. Secure the cable to the lance on the mounting bracket using

the cable tie provided.