Galaxy Rack-Mounted Vector Controller J85501M-1

3 - 2 Operation

Issue 2 January 2008

BD threshold default is set at 25.54V standard in 24V systems,
and 51.1V in 48V systems with slope thermal compensation
disabled. In systems with slope thermal compensation, the BD
threshold should be 0.5V below the slope upper temperature
voltage for 24V systems, and 1.0V below the slope upper
temperature voltage for 48V systems. The slope upper
temperature equals:

Float Set Point - (number of cells) · E · (F-D)
See Figure 3-1 for system settings E, F, and D

These levels generally avoid nuisance alarms from transient
conditions yet provide alarm indications early in a true BD
event, so that sufficient time is provided for maintenance
personnel to respond before battery reserve is exhausted. VLV
should be activated towards the end of the battery reserve
voltage to indicate a critical service condition.

Table 3-A: Alarm Identification Standard Assignments

Alarm Description

Alarm Status

Front Panel LED

GCM Relay

No active alarms present

Norm

Green

None

Very low voltage

Major

Red

None

Battery on discharge

Major

Red

BD

High float voltage

Minor

Yellow

None

Very high voltage

Major

Red

HV

Voltage sense fuse alarm

Major

Red

None

AC fail

Minor

Yellow

ACF

Multiple AC fail

Major

Red

ACF

Rectifier fail

Minor

Yellow

None

Multiple rectifier fail

Major

Red

None

Rectifier ID conflict

Major

Red

None

Rectifier manual off alarm

Minor

Yellow

None

Rectifier AC phase alarm

Minor

Yellow

None

Converter fail

Minor

Yellow

None

Multiple converter fail

Major

Red

None

Converter ID conflict

Minor

Yellow

None

Converter distribution alarm

Major

Red

MJF

Converter fan fail minor

Minor

Yellow

None

Converter fan fail major

Major

Red

None

Fuse alarm major

Major

Red

MJF

Auxiliary input major

Major

Red

None

Load Share imbalance

Minor

Yellow

None

Contactor 1 open

Major

Red

None

Contactor 1 failed

Major

Red

None

Contactor 2 open

Major

Red

None

Contactor 2 failed

Major

Red

None

High battery temperature

Major

Red

None

Temperature probe failure

Minor

Yellow

None

Maintenance open alarm

Major

Red

None