Galaxy Rack-Mounted Vector Controller J85501M-1

4 - 6 Installation and Configuration

Issue 2 January 2008

the default screen, press MENU twice. If no key is pressed for
approximately three minutes, the display will return to the
default front panel screen.

Refer to Table 4-A as each of the Configuration Parameters is
explained in the following sections. Each section also explains
how to access the data available from these features.

Table 4-A: Configuration Parameters

Main Menu

Heading

Parameter

Description

Range

(24V, 48V Systems)

Default (24V, 48V Systems)

Standard

Custom

Float Voltage

System float

voltage set point

22-28V, 44-56V

27.24V, 54.48V

27.24V, 54.48V

High float voltage

major alarm

25-30V, 50-60V

28.24V, 57V

28.5V, 57.0V

High float voltage

minor alarm

25-30V, 50-60V

27.74V, 56V

27.74, 56.0V

Battery discharge

major alarm

23-27.5V, 46-55V

25.54V, 51.1V

25.0V, 51.1V

Very low voltage

major alarm

20-25.5V, 40-51V

23.00V, 46.00V

23.0V, 46.0V

Rectifiers

Rectifier output

float current limit

30-110%

100%

110%

Number of

rectifiers on line

1-24

24, 1

24

Shunts

System shunt type

Battery, load, none

Battery

Battery

Shunt 1 current

rating

0-9999A

800A

1000A

Shunt 2 current

rating

0-9999A

0A

0A