Page 65: 5 troubleshooting, 5troubleshooting
Galaxy Rack-Mounted Vector Controller J85501M-1
Issue 2 January 2008
Troubleshooting 5 - 1
5
Troubleshooting
Replacing Circuit
Packs
Table 5-A lists the circuit packs available as replacements in the
Vector Controller.
Table 5-A: Replacement Circuit Packs and Temperature Modules
Designation
Description
Comcode
210E
Thermal Probe Multiplexer
107789513
BSM3
Modem Board
108415647
BSM4
Local Port Isolation Board
848501037
EBW1
Gateway Network Card
848733898
-
EBW Power Cable
848575841
GCM2
24V Vector Control Board
108890088
GCM3
48V Vector Control Board
108890096
--
LCD Display / Keypad Assembly
848733907
--
Alarm Board Header
406790188
1U-ALM
Alarm Termination Board
848711933
--
P5 Power Cable
848722096
Checking the
Highest Battery
Temperature
If temperature probes are connected to the controller and thermal
compensation is enabled, the highest battery temperature can be
calculated based on the plant voltage. Temperatures between the
battery thermal lower temperature and the battery thermal
nominal temperature can be calculated if the raising of system
voltage is also enabled.
Calculate the temperature as follows:
voltage difference
=
(system set point – system voltage reading)
cells per string
where cells per string is the number of 2-volt cells per string.