Galaxy Rack-Mounted Vector Controller J85501M-1

Issue 2 January 2008

Troubleshooting 5 - 1

5

Troubleshooting

Replacing Circuit

Packs

Table 5-A lists the circuit packs available as replacements in the
Vector Controller.

Table 5-A: Replacement Circuit Packs and Temperature Modules

Designation

Description

Comcode

210E

Thermal Probe Multiplexer

107789513

BSM3

Modem Board

108415647

BSM4

Local Port Isolation Board

848501037

EBW1

Gateway Network Card

848733898

-

EBW Power Cable

848575841

GCM2

24V Vector Control Board

108890088

GCM3

48V Vector Control Board

108890096

--

LCD Display / Keypad Assembly

848733907

--

Alarm Board Header

406790188

1U-ALM

Alarm Termination Board

848711933

--

P5 Power Cable

848722096

Checking the

Highest Battery

Temperature

If temperature probes are connected to the controller and thermal
compensation is enabled, the highest battery temperature can be
calculated based on the plant voltage. Temperatures between the
battery thermal lower temperature and the battery thermal
nominal temperature can be calculated if the raising of system
voltage is also enabled.

Calculate the temperature as follows:


voltage difference


=

(system set point – system voltage reading)

cells per string

where cells per string is the number of 2-volt cells per string.