Galaxy Rack-Mounted Vector Controller J85501M-1

Issue 2 January 2008

Product Description 2 - 11

Control Signal Inputs

Table 2-H: BUJ1 Control Signal Inputs

Signal

Description

Alarm

Board

Alarm Asserted

PBT

Plant Battery Test

TB4.8

Closure to PBT_RTN (TB4.7)

RO

Reserve Operation

TB4.4

Closure to Batt

See Section 3 for details on the Plant Battery Test and Reserve
Operation features.

Thermal Probe

Connections

Four thermistor or 210E module inputs are provided on the
alarm termination board, and two thermal probe inputs are
provided at J1 and J3 on the BUJ1. These connectors will accept
standard Lineage Power thermal cables or 210E cables. J1 and
J3 provide cable access to RTH1 and RTH2 thermal probes,
respectively. If connections are made at J1 and J3 then they
should not be made at the terminal blocks and vice versa. Access
to all four thermistors is available at the terminal block. Each
thermistor is connected to the RTH#+ and RTN#, where # = 1
through 4. A strap is required across RTH#+ and EN#+ for each
thermistor input used. The strap is not required when using 210E
modules.

RTH ALM, RTH ALMR: Thermistor alarm input and return
from 210E module. See Section 4 for 210E module connections.

Table 2-I: RTH ALM, RTH ALMR Terminals

Signal

Terminal

Signal

Terminal

RTH1_EN

TB6.7

RTH3_RTN

TB5.11

RTH1_RTN

TB6.8

RTH3+

TB5.12

RTH1+

TB6.9

RTH4_EN

TB5.6

RTH2_EN

TB6.3

RTH4_RTN

TB5.7

TRH2.RTN

TB6.4

RTH4+

TB5.8

RTH2+

TB6.5

RTH_ALM

TB6.11

RTH3_EN

TB5.10

RTH_ALMR

TB6.12

Rectifier Connections

J7, J8: RJ45 connectors for the serial RS-485 rectifier and
equipment interface. These are parallel connectors and can be
used interchangeably.

Communication Port

J5: RS-232 serial communication port used with the optional
BSM3 modem boards or EBW1 Gateway board (see Appendix
A).

Advertising