Galaxy Rack-Mounted Vector Controller J85501M-1

Issue 2 January 2008

Installation and Configuration 4 - 9

Battery Discharge

Test Results

After initiating a Battery Discharge Test through the Operations
menu, the user obtains the data or results from a battery
discharge test through the View Status menus. Selecting
Batteries

> Battery Test Result displays the result of the last

battery test. The Vector stores the result of the last completed
test. This is the recorded data (not manually changeable) for the
battery test result. Refer to the battery discharge test operation
for detail test procedure and results.

Pressing the Battery Test Result softkey displays an indication
of the last battery test performed. The display indicates either
that the test was completed or not completed. In addition, the last
completed battery test results are saved and can be accessed by
pressing the “

< View Completed” softkey. This allows the user

to observe the reserve time and load current during the test. If for
some reason the test was completed and results were
unsatisfactory, the message “Check Battery” is displayed. If the
last test was interrupted, the message “Not Available” is
displayed. If a test was stopped before completion, the phrase
“Previous Test Was Interrupted” will also appear when the
Battery Test softkey is pressed.

Communication

ports

Local port baud rate

setting

Auto/1200 to 19,200

Auto

Auto

Local port flow

control setting

None/SW/HW

None

None

Modem port baud

rate setting

Auto/1200 to 19,200

2400

2400

Modem port flow

control setting

None/SW/HW

None

None

Number of rings

before modem

answers

1 to 9

1

1

Calibrate to meter

Calibrate system

voltage to a new

value

22-28V, 44-56V

System voltage

N/A

Calibrate converter

voltage to a new

value

46-57V

Converter voltage

N/A

Table 4-A: Configuration Parameters (Continued)

Main Menu

Heading

Parameter

Description

Range

(24V, 48V Systems)

Default (24V, 48V Systems)

Standard

Custom