Digital general function card – GE Industrial Solutions 6KCV301DGF User Manual

Page 10

Advertising
background image

—————— Digital General Function Card ——————

10

GEI-100430

RS485

RS232

PC/PLC

RS232

5 9 6 8 3 7

X3 RS485

DGFC

S23=ON

S24=ON

Figure 1.2.2.2: RS-485 single point comm. without signal isolation

The DGF jumpers are:

Name

Default

Function

S23

ON

"ON" RS-485 line end device (for terminal resistor)

S24

ON

"ON" RS-485 line end device (for terminal resistor)

d0020g

Figure 1.2.2.3 shows an RS-485 communications link with three 6KCV301DGF cards
with signal isolation.This is the recommended configuration for applications that use
the serial link. The card at the end of the line (both ends) must have the terminator
resistor inserted, and thus S23=S24=ON while the other two 6KCV301DGF cards
must have S23=S24=OFF.

5 9

3 7

5 9

3 7

5 9

3 7

X3 RS485

X3 RS485

X3 RS485

DGFC

DGFC

DGFC

S23=OFF

S24=OFF

S23=OFF

S24=OFF

S23=ON

S24=ON

COM

+5V

RS485

Figure1.2.2.3: RS-485 communications with signal isolation

DGF connectors are female connectors. In this configuration, all 6KCV301DGF cards
need external power supply for serial interface.