GE Industrial Solutions 6KCV301DGF User Manual
Page 54
—————— Digital General Function Card ——————
54
GEI-100430
[501]
PERIOD_TIM
Period scan time in msec.
With synchronous operation, a multiple of 2 will be accepted.
[502]
PERIOD_REA
Period real scan time in msec (example 10 = 10
msec). This is the period that has been accepted
by the DGF.
With PERIOD_MODE at 2 this is equal to
PERIOD_TIM
With PERIOD_MODE at 1 this is a multiple of
2 of PERIOD_TIM(rounded up)
[503]
AB_RESALL
Enable reset alarms
This parameter selects the source that determines the end of the alert status (transition
Alert-Ready). Possible values are the following:
0 =
transition enabled via DGF serial line S-LINK3,
drive keypad or field bus
1 =
transition through drive alarm reset
2 =
transition via digital input of the optional I/O
card. In case 0, the transition is performed by
writing the parameter WSTATO[506]. In case
1, the DGF exits from the Alert status
automatically when the alarm status on the drive
is reset. In case 2 the DGF exits from the Alert
status by using the digital input of the optional
I/O card.
[504]
AB_RUN
Transitions READY - RUN and RUN - READY
It determines the conditions for READ Y-RUN and RUN - READY transition.
Possible values are:
0 =
only the transition via serial line S-LINK3 or
field bus is active
1 =
only the automatic transition with drive enable/
disable is active
2 =
transition via digital input of I/O optional card
(see also “AUTO-RUN” [508]).
[506]
WSTATO
Status of the DGF
This parameter displays the status of the card. If it is written, it allows changing the
DGF status.