7 how to configure the dgf – GE Industrial Solutions 6KCV301DGF User Manual

Page 56

Advertising
background image

—————— Digital General Function Card ——————

56

GEI-100430

When the period is activated by the drive(PERIOD_MODE=1) this
parameter indicates the number of times that the synchronous period
takes longer than PERIOD_TIM. This parameter must be always 0.

[510]

SBORD ASYN

Number of times the period exceeds
PERIOD_TIM

When the period is activated by the DGF(PERIOD_MODE=2) this
parameter indicates the number of times that the asynchronous period
takes longer than PERIOD_TIM. This parameter must be always 0.

[511]

ADDRESS

Address of the card for SLINK 3

It is used to write the Slink3 address of the DGF. If written, the value
is copied and saved in parameter [3] “ACT-ADDR”.
Note: the address of the serial line cannot be saved in a parameter
file.

[512]

Real time

Maximum real period time

This is the maximum number of milliseconds taken by the user
program to execute the period.

[555]

CMD_REMOTE Remote command
It allows the receiving of DBASE commands via the serial line of
the drive or via a communication card. Possible commands:

CODE

COMMAND

310

Save Dbase parameters

311

Load Dbase parameters

312

Check Dbase parameters

313

Init. Dbase parameters

d0350g