Table 2.2.2.4: alarm code 14 (al_bricks_dp) cause, Table 2.2.2.5: alarm code 15 (al_register) cause, Table 2.2.2.6: alarm code 16 (al_ccz) cause – GE Industrial Solutions 6KCV301DGF User Manual
Page 35
35
—————— Digital General Function Card ——————
6KCV301DGF
Alarm CODE 8:
generated via the DGF serial line.
Alarm CODE 11:
unknown block. The program contains an unknown block.
Check the scheme.
Alarm CODE 12:
alarm generated by the application program or Win+Drive via
an ALL block.
E.g.: space error in a system like “ELECTRICAL AXIS” or
block for this alarm is used in the application.
Alarm CODE 13:
generated if the program contains a call to an invalid I/O block
(I/O optional cards).
Verify the connections in your scheme I/O blocks.
Alarm CODE 14:
software alarm in the DPRAM interface due to a wrong
conversion of the read or written value.
Verify the DPRAM block setting on the scheme (e.g. FLOAT to
integer).
CAUSE
NAME
DESCRIPTION
0..99
AL_BRICK_DP_S_IE
INT—>EXT syn
100..199 AL_BRICK_DP_S_EI
EXT—>INT syn
200..299 AL_BRICK_DP_A_IE
INT—>EXT asyn
300..399 AL_BRICK_DP_A_EI
EXT—>INT asyn
d0150g
Table 2.2.2.4: Alarm code 14 (AL_BRICKS_DP) cause
Alarm CODE 15, 17,30: DGFCy internal software alarms.
CAUSE
NAME
DESCRIPTION
1
AL_FS
FS register alarm
2
AL_GS
GS register alarm
d0160g
Table 2.2.2.5: Alarm code 15 (AL_REGISTER) cause
Alarm CODE 16:
CCZ hardware alarm, signaling a hardware malfunction of
the card. Replace the card or check X0 connector.
CAUSE
NAME
DESCRIPTION
1
ALC_CCZ_1
CCZ not false at start
2
ALC_CCZ_2
CCZ not true at start
3
ALC_CCZ_3
CCZ is at first FALSE and then TRUE
d0170g
Table 2.2.2.6: Alarm code 16 (AL_CCZ) cause
Alarm CODE 18:
generated if the DGF time base is different from drive time
base. See the system parameter value (IPA 500 up to IPA600)
Alarm CODE 20:
Win+Drive configuration alarm. Verify the DPRAM block
setting on the scheme (e.g. DPRAM configuration error).
Alarm CODE 21:
Win+Drive execution alarm.
Alarm CODE 22:
DeviceNet. See Dnet Manual.