1 alarm code from the drive, 2 severe alarm, Table 2.2.2.7: alarm code 22 (al_dnet) cause – GE Industrial Solutions 6KCV301DGF User Manual
Page 36
—————— Digital General Function Card ——————
36
GEI-100430
CAUSE
NAME
DESCRIPTION
0..1000
ALC_WFIX
WFIX brick alarm
1000..1999 ALC_RFIX
RFIX brick alarm
2000..3999 ALC_CFIX
CFIX brick alarm
10000
ALC_M10_TIMEOUT
Time-out mode 10
d0180g
Table 2.2.2.7: Alarm code 22 (AL_DNET) cause
2.2.2.1 Alarm code from the drive
The following ALARM CODES are generated by the drive if it detects a malfunction
with the DGF.
Replace DGF or Regulation card, check XO connections
CODE
NAME
TYPE
DESCRIPTION
100 AL_DPRAM_DRV
1
DPRAM communications on Drive
101 AL_CCZ_DRV
2
CCZ hardware on drive
d0190g
Alarm 100 (AL_DPRAM_DRV): ALARM CAUSES
CAUSE
NAME
DESCRIPTION
1
AL_WD_SW
Software watchdog on drive
2
AL_CHK_KEY
Checksum err. on keypad communication
3
AL_CFG_OPAZ_LP
Configuration err. IE-ASYN
4
AL_CHK_OPAZ_LP
Checksum err. IE-ASYN
5
AL_CFG_OPAZ_HP
Configuration err. IE-SYN
6
AL_SEM_OPAZ_HP
Semaphore IE-SYN
7
AL_LWR_OPAZ_HP
Last write IE-SYN
8
AL_CHK_OPAZ_HP
Checksum IE-SYN
9
AL_CFG_AZOP_LP
Configuration EI-ASYN
10
AL_CFG_AZOP_HP
Configuration EI-SYN
11
AL_SEM_AZOP_HP
Semaphore EI-SYN
12
AL_LWR_AZOP_HP
Last write EI-SYN
13
AL_SYNC_WD
Watch dog synchronization alarm
99
AL_GEN_DPRAM
Drive DPRAM structure has been
disabled
111
OPT2_TMO_SINCRO
Synchronization timeout
d0200g
2.2.2.2 Severe alarm
It is not always possible for the DGFCy to recover from an unexpected condition. In
this case all functionality of the card is disabled. The DGFCy starts blinking LEDs
H1,H2,H3 and H4. The following table describes the type of these errors. The exception
ID is the number that is blinked on the LEDs.