—————— Digital General Function Card ——————

6KCV301DGF

Possible values are :

VALUE

STATUS

0

Reserved (NULL (#) )

1

Reserved (SINCRO (#) )

2

IDLE

3

READY

4

Reserved (SINGLE (#) )

5

RUN

7

ALERT

8 (*)

RESALL (*)

d0340g

(*) By writing this value an alarm reset will be performed

(#) Special status, not to be used (reserved only to factory)

Note that the transitions Ready - Run and the alarm reset occur via AB_RUN and
AB_RESALL parameters. Therefore, this parameter can be used to write the new
status only if the serial communication, keypad or field bus is enabled (AB_RUN
and/or AB_RESALL equal to 0).

[507]

EN_LAST

Reserved

[508]

AUTO_RUN

Automatic RUN status

When the card is supplied power, AUTO_RUN controls the automatic
transition

READY-RUN, if the necessary operating conditions are satisfied.
The transition depends on the “AB_RUN” parameter setting.
The possible configurations are as follows:

AUTO_RUN = 0 : the automatic transition is not carried out.

AUTO_RUN = 1

AB_RUN = 0 : the transition READY-RUN is

carried out automatically one time. To set the card in READY again,
a command via serial line SLINK3, keypad or field bus is necessary
AUTO_RUN = 1

AB_RUN = 1 : the card remains in READY

condition until the drive is disabled.

AUTO_RUN = 1

AB_RUN = 2 : the card remains in READY

condition until the appropriate digital input of the optional I/O card
is set to high level

AUTO_RUN =2

ABI_RUN=1

The control reaches directly the run condition and ir remain here in
spite of possible ALARM condition of the drive.

For each of these configurations, it is necessary that initial conditions
move the card into the READY status. If this does not occur, the
card remains in the IDLE state.

[509]

SBORD SYN

Number of times the period exceeds
PERIOD_TIM