Positioner 1067 appendix – Burkert Type 1067 User Manual

Page 100

Advertising
background image

E-48-

POSITIONER 1067

APPENDIX

Connection

1) As potential free contacts

- connect the cables to the O5 and O6 or O7 and O8 terminals according to the connection
schematic
- place the jumper on the "REL" position (see figure below)

2) For connecting receivers to the outputs O6 and O8 (operating voltage of 24 V DC)

- connect the cables to the terminals O6 and O8 and to GND3 and GND4 according to the

connection schematic below.

For inductive receivers, use the recovery diode.

- place the jumper on the "U

out

" position (see figure below)

Short-circuit hazard

: before closing the device, make sure the screws of the connection

block are tightened.

- Close the cover and tighten the 4 screws, making sure the cables are not wedged in.

Confi guration
- Configurate the positioner as described in chapter 4.5.
- Activate the binary position indication or the Booster function by choosing either the BINARY

or the BOOST option in the OUTPUT function.

!

!