Positioner 1067, 4 operation – Burkert Type 1067 User Manual

Page 87

Advertising
background image

POSITIONER 1067

E-35-

4 OPERATION

BIN-IN

(factory setting: INACTIVE): Binary input.

The action of the binary input (contact) can be specified by means of this additional function.
Options:

INACTIVE:

Binary input is not active.

SAFEPOS

(safety position): Input of a safety position SPOS selected if necessary.

Setting range: 0 ... 100% of the stroke range (factory setting: SPOS = 0).

NORM OPN

(normalyl open): Binary input in de-energised position open (normally-

open contact or closer). Safety position is adopted when the contact closes.

NORM CLS

(normally closed): Binary input in de-energised position closed (normally-

closed contact or opener). Safety position is adopted when the contact opens.

OUTPUT

(option): (Additional function only activable with optional board.)

- ANALOG

Analog or process position feedback (4...20 mA) (see Appendix 3)

- BINARY

Programmable Binary output (see Appendix 4)

XDO

Alarm deviation value exceeds XD

XD

Deviation limit value ; Setting range: 0,1 ... 20% (Factory setting 1%)

NORM OPN

Binary output normally open

NORM CLS Binary output normally closed

- ALARM

Alarm signal, XMIN or XMAX threshold reached

XMIN

Low alarm limit value ; Setting range: 0...100%

NORM OPN

Binary output XMIN normally open

NORM CLS

Binary output XMIN normally closed

XMAX

High alarm limit value ; Setting range: 0 ... 100%

NORM OPN

Binary output XMAX normally open

NORM CLS

Binary output XMAX normally closed

BOOST

Signal output for external Booster valve (see Appendix 4)

CODE

(factory setting: 0000) User code. The positioner can be protected from unauthorised operation

by means of a 4-digit user code. 2 Levels of protection are available.
MENU+M/A:

All functions protected by the user-code

MENU:

Access to configuration menu restricted. MANU/AUTO switching and change

of process values are free (cf § 4.4.1).

Setting range: 0000 ... 9999

Regardless of the possibility of the existence of a preset code, there is a fixed programmed master
code which when entered enables all control operations to be performed.

ADDFUNCT

(Additional functions): Additional functions.

This enables additional functions to be taken into the main menu and then removed (see § 4.5.2).

AUTOTUNE:

Automatic parametering.

This function enables the program for automatic adaptation of the actuator to the valve in use to be
started. The following functions are automatically initiated (see section 4.3):
- The sensor signal is matched to the (physical) lift of the continuous valve,
- The parameters of the PWM signals are determined in order to control the internal magnetic valves,
- The parameters of the position controller are adjusted optimally.
This automatic setting of parameters is completed in approximately 30-120 seconds.

END:

End of configuration menu.

(The software version is displayed on the right margin of the display). This menu item enables the confi-
guration menu to be left by operation of the MANUAL/AUTOMATIC key (cf § 4.3).