POSITIONER 1067

APPENDIX

A3 :

OPTION BOARD "4-20 mA ANALOG POSITION INDICATION"

(IDENT. 427193G): MOUNTING AND CONNECTION

The positioner must be equipped with the software version F, or higher. Check it in the main
menu, option END: it is displayed at the right-hand side of the screen.

Technical characteristics of the Option output of the positioner
- Output signal for the current value : 4-20 mA
- External working resistance / Input resistance of a connected device : 0-560 Ohms
- Output error rate : < 0,05 %
- Potential free output ; electrically separated from the position electronics.

Mounting
- Disconnect the positioner from the voltage supply
- Unscrew the 4 screws of the positioner cover and open the cover
- Remove the 2 red jumpers from the motherboard
- Insert the optional board onto the motherboard (see figure below)

Make sure the pins correctly slide into the motherboard.

- Pass the cables through one of the 2 PG9 cable glands, dismantle them over 6 mm and

connect them to the connection block according to the connection schematic (terminals I/O3

and

I/O4)

- Close the cover and tighten the 4 screws, making sure neither the cables nor the wires are
wedged

in.

Connection diagram

Confi guration
- Configurate the positioner as described in chapter 4.5.
- Activate the analog position indication by choosing the ANALOG option of the OUTPUT
function

Analog Option board

Motherboard

pins

!

!

I1

U1

GND1

I2

GND2

I/O1

I/O2

I/O3

I/O4

PE

+24 V

-

0-10 V

0/4-20 mA

4-20 mA

I

L

= 4-20 mA

R

L

= 0-560 Ohm

24 V DC Supply Voltage

Analog Option board

Motherboard

+
-