Positioner 1067, 4 operation – Burkert Type 1067 User Manual

Page 71

Advertising
background image

POSITIONER 1067

E-19-

4 OPERATION

4.3 Setting up

The following basic settings are to be carried out on the initial setting up (commissioning) of the posi-
tioner in conjunction with the valve (specification of basic functions):
- Specification of the positional feedback of the continuous valve to the positional transducer (direct or

lever),

- Specification of the unit signal input chosen for entering the set position (0 ... 20 mA, 4 ... 20 mA or 0

... 10 V),

- Initiating the automatic adaptation of the actuator to the valve being used.

When the power is switched on, the positioner is in the process control level. It is necessary to switch
to the configuration level for specification of the basic functions. To do this, press the MANUAL/AUTO-
MATIC key and hold for 5 seconds. The first menu point X-SENS of the main menu is then displayed.

Fig. 24 Main menu for fi rst setting up

Function

AUTOMATIC

or

MANUAL

after 30 to 120 sec.

BLINKING

Advertising