5 technical data – Burkert Type 1067 User Manual

Page 60

Advertising
background image

E-8-

POSITIONER 1067

2 DESCRIPTION

2.5 Technical data

Electrical data
Power supply:

24 VDC ±10%, residual ripple 10%, No industrial DC

Power consumption:

< 10 W

Input for desired value
Input for setpoint for position or process control:

- Unit signal

4 ... 20 mA

- Unit signal

0 ... 20 mA

- Unit signal

0 ... 10 V

Input for process signal (in case of process control):

- Unit signal

4 ... 20 mA

Binary input:

Can be configured as a normally open or normally

closed

contact.

Terminations: 1.5

mm

2

bolted terminals

Two cable glands

Pneumatic data
Control medium:

filtered compressed dry air, oiled or non-oiled

Dust content

class 4,

max. particle size 15 µm,

max. particle density 8 mg/m

3

Dew point

class 4 (+3 °C)

Oil content

class 5, max. 25 mg/m

3

Pressure range:

0 ... 6 bar

Air rates
Inlet valve:

23 Nl / min

(1)

Exhaust valve:

25 Nl / min

(1)

Air consumption by unit
in stable state:

0 Nl / min

Unions:

G 1/8" internal thread

(1)

When pressure reduction from 6 to 5 bar

Mechanical data
Regulation range of internal path-measuring system:

lift turn: 10...80 mm

rotary movement: 0...180°

Regulation range of external path-measuring system:

lift turn: 0...50 mm

Process controller data
Proportional correction value KP:

0...99,99

Reset time TN:

0.5...999.9

Rate time TV:

0.0...999.9

Operating point:

0...100%

Installation and operating data
External dimensions of positioner :

125 mm x 80 mm x 80 mm (W x H x D)

Material of body:

Aluminium, lacquered

Material of the fluid plate:

Aluminium, anodised

Weight of positioner:

Approx. 1 kg

Degree of protection:

IP 65

Operating temperature:

0 ... 60 °C