POSITIONER 1067

E-23-

4 OPERATION

4.5 Configuration

4.5.1 Additional functions

The operating concept of the positioner is based on a strict separation between basic and additional
functions. Only the basic functions are activated in the delivery state of the unit. These enable the
unit-specific basic settings to be carried out on the initial setting up (cf § 4.3). These are adequate for
normal operation. For more demanding tasks of position and process control, additional functions which
have been preset in the configuration level, can be selected and specified.
The additional functions are listed below. For further informations about these functions , see § 4.5.4.

Fig. 27 Additional functions

Additional Parameter

Description

function

ACTUATE

Function of actuator

-

SINGLE

INTERN

Single acting actuator with intern or without boost valves

BOOST

Single acting actuator with extern boost valves

- DOUBLE

- Double acting actuator

CHARACT

Selection of the transmission characteristic curve between the

input signal and stroke (correction characteristic curve)

- LINEAR

- Linear characteristic curve

- 1 : 25

- Equal percentage characteristic line with a rangeability of 1 : 25

- 1 : 50

- Equal percentage characteristic line with a rangeability of 1 : 50

- 25 : 1

- Inverse equal percentage characteristic with a

rangeability of 25 : 1

- 50 :1

-Inverse equal percentage characteristic with a

rangeability of 50 : 1

- FREE

- User-defined, characteristic line freely programmable

DEADBND

- DBD

Dead band with regard to the closed tight function system deviation

CLTIGHT

Close tight function

- CLT

- Closed tight threshold

DIRECTN

WPOS

Relationship between input signal and measure

- RISE

- Direct direction of action

- FALL

- Inverse direction of action

XPOS

Relationship between ventilation of the actuators chamber A1

and the setpoint

- RISE

- Direct direction of action

- FALL

- Inverse direction of action

SPLTRNG

Signal range splitting, input signal in % for the complete stroke

range through which the valve passes

- MIN

- Input of minimum value of input signal.

- MAX

- Input of maximum value of input signal.