Burkert Type 1067 User Manual

Page 84

Advertising
background image

E-32-

POSITIONER 1067

4 OPERATION

DIRECTN

(FACTORY SETTING: WPOS = RISE, XPOS = RISE): Sense or direction of action.

By means of the WPOS additional function the sense of action between the input signal and the
setpoint (WPOS). can be set, and also by means of XPOS the assignment of the air supply state of the
actuator A1 to the indicated value (XPOS).

Setting range:
MIN:

0 ... 75 % of the unit signal range,

MAX:

25 ... 100 % of the unit signal range.

The minimum distance between MIN and MAX is 25%.

SPLTRNG

(factory setting: MIN = 0%, MAX = 100%): Split range

This additional function enables the set value range of a positioner to be restricted by stipulating a mini-
mum and maximum value. This makes it possible to divide the used unit signal range (0 ... 10 V, 0 ... 20
mA or 4 ... 20 mA) over several positioners (without or with an overlap). In this way, several valves can
be partially used either simultaneously or in sequence as a final controlling element
(Fig. 35).

Fig. 35 Splitting a unit signal range into two set value ranges

Setpoint (mA)

Setpoint range
positioner 1

Setpoint range
positioner 2

Plug travel (%)

Input DIRECTN

Setpoint

WPOS
I1 U1

(WPOS)

0/4 mA

0 V RISE

0 %

20 mA

10 V

100 %

0/4 mA

0 V

FALL

100 %

20 mA

10 V

0 %

Air supply

DIRECTN

Measure

State A1

XPOS

(XPOS)

Air exhaust

RISE

0 %

Air on

100 %

Air exhaust

FALL

100 %

Air on

0 %

Fig. 34 Sense of action

0/4 mA Input signal

20 mA

0 V

10 V

air exhaust

air on

Air supply state

FALL

RISE

FALL

RISE