DIN-MON™ SMART METER

62-0442—04

28

NOTE: If you have connected the current sensor to all terminals and the error

message is still appearing, reverse the black and white wires and repeat

the previous steps until the correct connection is found. If the CT Error

message is eliminated, you have found the correct sensor connection;

however, the current sensor was not installed properly around the con-

ductor, or the sensor wires were extended and not spliced together cor-

rectly.

Correct the sensor installation by reconnecting the black wire to the

black terminal and the white wire to the white terminal on the plug and

reinstall the plug into the correct phase terminal for that current sensor.

The error message should be eliminated and the current sensor is now

installed properly.

If the CT Error message has not been eliminated at any time while trying all 3 inputs

both ways, check the AC voltage output from the current sensor leads between the

black and white wires using an AC voltmeter. If the reading on the AC voltmeter is

close to or at zero, this indicates a very light load on the circuit or that the current

sensors are not secured properly (check connection between current sensor halves or

the lead splices to ensure they are tight).

Once the first current sensor is connected properly and the error message has been

eliminated, repeat the previous procedure for the remaining current sensor(s). When

all error messages have been eliminated and all sensors are installed correctly, the

meter is operational.

When the meter is properly connected, replace Mains / Current Sensor cover and

secure with cover screw.

Wait 5 seconds and check the meter display.