7.2.9 Setting CT Selection

To change the CT Selection, complete the following steps:

1. Press MENU button.

2. Use UP or DOWN button until the arrow is on the CT

SELECTION line.

3. Press SELECT button.

4. Use UP or DOWN button to make changes.

5. Press SELECT button to advance to the next setting. Repeat this step until all

the CT selection settings have been updated.

6. Press MENU to complete the changes. If changes were made, you’ll be asked to

save changes.

7. Press UP or DOWN to select ‘Y’ or ‘N’.

8. Press SELECT button to accept the selection. This will return you to the main

menu.

9. Select EXIT to get out of programming mode and return to normal display mode.

FIELD RANGE: CT TYPE=[Split or Solid]; CT SIZE=[50, 100, 200, 400, 800] Amps

7.2.10 Setting Access Protection

To change the Access Protection, complete the following

steps:

1. Press MENU button.

2. Use UP or DOWN button until the arrow is on the

ACCESS PROTECT line.

3. Press SELECT button.

4. Use UP or DOWN button to make changes.

5. Press SELECT button to advance to the next setting. Repeat this step until all

the Access Protection settings have been updated.

6. Press MENU to complete the changes. If changes were made, you’ll be asked to

save changes.

7. Press UP or DOWN to select ‘Y’ or ‘N’.

8. Press SELECT button to accept the selection. This will return you to the main

menu.

9. Select EXIT to get out of programming mode and return to normal display mode.

FIELD RANGE: REMOTE=[Y or N]; LCD=[Y or N]

CT TYPE

SPLIT

CT SIZE

200

ACCESS PROTECT

REMOTE

Y

LCD

Y