Appendix a: modbus point map – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 58

Advertising
background image

DIN-MON™ SMART METER

62-0442—04

58

APPENDIX A: MODBUS POINT MAP

ADDRESS REG

TYPE

DESCRIPTION

UNITS

R/W

40001

1

2

Integer

Energy delivered

Wh Pulse

R/W

40003

1

2

Integer

Energy received

Wh Pulse

R/W

40005

1

2

Integer

Reactive energy delivered

VARh Pulse

R/W

40007

1

2

Integer

Reactive energy received

VARh Pulse

R/W

41001

1

2

Float

Energy delivered

kWh

R/W

41003

1

2

Float

Energy received

kWh

R/W

41005

1

2

Float

Reactive energy delivered

kVARh

R/W

41007

1

2

Float

Reactive energy received

kVARh

R/W

41009

2

Float

Real power

kW

R

41011

2

Float

Reactive power

kVAR

R

41013

2

Float

Apparent power

kVA

R

41015

2

Float

Power factor

% PF

R

41017

2

Float

Peak demand

kW

R/W

41019

2

Float

Current average

Amps

R

41021

2

Float

Voltage line-neutral

Volts-N

R

41023

2

Float

Voltage line-line

Volts-L

R

41025

2

Float

Frequency

Hz

R

41027

2

Float

Phase angle

Degree

R

41029

2

Float

Real power, phase A

kW

R

41031

2

Float

Real power, phase B

kW

R

41033

2

Float

Real power, phase C

kW

R

41035

2

Float

Reactive power, phase A

kVAR

R

41037

2

Float

Reactive power, phase B

kVAR

R

41039

2

Float

Reactive power, phase C

kVAR

R

41041

2

Float

Apparent power, phase A

kVA

R

41043

2

Float

Apparent power, phase B

kVA

R

41045

2

Float

Apparent power, phase C

kVA

R

41047

2

Float

Power factor, phase A

% PF

R

41049

2

Float

Power factor, phase B

% PF

R

41051

2

Float

Power factor, phase C

% PF

R

41053

2

Float

Current, phase A

Amps

R

41055

2

Float

Current, phase B

Amps

R

41057

2

Float

Current, phase C

Amps

R

41059

2

Float

Voltage, line phase A to N

Volts-N

R

Advertising