Appendix c: lonworks protocol data points – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 63

Advertising
background image

DIN-MON™ SMART METER

63

62-0442—04

APPENDIX C: LONWORKS PROTOCOL DATA POINTS

NETWORK VAR

BLK VAR

SNVT

DESCRIPTION

UNITS

R/W

nvoWh_DelPulse

1

1

3

SNVT_count_32

Energy delivered pulse

Wh Pulse

R

nvoWh_RecPulse

1

2

4

SNVT_count_32

Energy received pulse

Wh Pulse

R

nvoVARh_RecPulse

1

3

5

SNVT_count_32

Reactive energy

delivered

VARh

R

nvoVARh_DelPulse

1

4

6

SNVT_count_32

Reactive energy received

VARh

R

nvoKWh_Del

1

5

7

SNVT_count_inc_f Energy delivered

kWh

R

nvoKWh_Rec

1

6

8

SNVT_count_inc_f Energy received

kWh

R

nvoKVARh_Del

1

7

9

SNVT_count_inc_f Reactive energy

delivered

kVARh

R

nvoKVARh_Rec

1

8

10

SNVT_count_inc_f Reactive energy received

kVARh

R

nvoReal_Pwr

9

11

SNVT_count_inc_f Real power

kW

R

nvoReact_Pwr

10

12

SNVT_count_inc_f Reactive power

kVAR

R

nvoAppar_Pwr

11

13

SNVT_count_inc_f Apparent power

kVA

R

nvoPwr_Fact

12

14

SNVT_pwr_fact_f

Power factor

% PF

R

nvoPeak_Dem 1

13

15

SNVT_count_inc_f Peak demand

kW

R

nvoCurrent_Avg

14

16

SNVT_amp_f

Current average

Amps

R

nvoVolt_LN

15

17

SNVT_volt_f

Voltage line-neutral

Volts-N

R

nvoVolt_LL

16

18

SNVT_volt_f

Voltage line-line

Volts-L

R

nvoFrequency

17

19

SNVT_freq_f

Freq.

Hz

R

nvoPhase_Angle

18

20

SNVT_count_inc_f Phase angle

Degree

R

nvoReal_Pwr_PhA

19

21

SNVT_count_inc_f Real power, phase A

kW

R

nvoReal_Pwr_PhB

20

22

SNVT_count_inc_f Real power, phase B

kW

R

nvoReal_Pwr_PhC

21

23

SNVT_count_inc_f Real power, phase C

kW

R

nvoReact_Pwr_PhA

22

24

SNVT_count_inc_f Reactive power, phase A

kVAR

R

nvoReact_Pwr_PhB

23

25

SNVT_count_inc_f Reactive power, phase B

kVAR

R

nvoReact_Pwr_PhC

24

26

SNVT_count_inc_f Reactive power, phase C

kVAR

R

nvoAppar_Pwr_PhA

25

27

SNVT_count_inc_f Apparent power, phase

kVA

R

nvoAppar_Pwr_PhB

26

28

SNVT_count_inc_f Apparent power, phase

kVA

R

nvoAppar_Pwr_PhC

27

29

SNVT_count_inc_f Apparent power, phase

kVA

R

nvoPwr_Fact_PhA

28

30

SNVT_pwr_fact_f

Power factor, Ph. A

% PF

R

nvoPwr_Fact_PhB

29

31

SNVT_pwr_fact_f

Power factor, Ph. B

% PF

R

nvoPwr_Fact_PhC

30

32

SNVT_pwr_fact_f

Power factor, Ph. C

% PF

R

nvoCurrent_PhA

31

33

SNVT_amp_f

Current, phase A

Amps

R

nvoCurrent_PhB

32

34

SNVT_amp_f

Current, phase B

Amps

R

nvoCurrent_PhC

33

35

SNVT_amp_f

Current, phase C

Amps

R

nvoVolt_LN_PhA_N

34

36

SNVT_volt_f

Voltage line-neutral

phase A-N

Volts-N R

nvoVolt_LN_PhB_N

35

37

SNVT_volt_f

Voltage line-neutral

phase B-N

Volts-N R

nvoVolt_LN_PhC_N

36

38

SNVT_volt_f

Voltage, line-neutral

phase C-N

Volts-N R

*

NOTE: BLK = Function Block, VAR = Lon Network Variable, SNVT = Standard Network Variable Type