E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 65

Advertising
background image

DIN-MON™ SMART METER

65

62-0442—04

NOTE

DESCRIPTION

1

To clear kWh and kVARh, set nviResetUsageCh to 1.

To clear nvoExt_Input_1, set nviResetUsageCh to 2.

To clear nvoExt_Input_2, set nviResetUsageCh to 3.

To clear nvoPeak_Dem, set nviResetUsageCh to 4.

2

To set the real time clock, set nviRTC_DateTime to the desired date and time.

3

nvoIntervalData will display the number of pulses for the selected interval period and

channel. For example: set nviIntDataTime to 6/1/2012 13:15:00 to read the number of pulses

from 13:15:00 to 13:29:59. The second status bit value will be 0 if no error has occurred.

nviIntDataPeriod will select the interval data of 15 or 5 minutes. This value will not change

the default interval data period value of 15 minutes.

nviIntDataChan will select the usage channel. For example, set nviIntDataChan to 1 to read

the interval data for nvoKWh_Del. Set nviIntDataChan to 2 to read the interval data for

nvoKVARh_Del. Set nviIntDataChan to 3 to read the interval data for nvoKWh_Rec. Set

nviIntDataChan to 4 to read the interval data for nvoKVARh_Rec.

4

nviRequest commands can disable or enable functional blocks. Any changes will be saved

even after powered down.

Set nviRequest to 0,RQ_DISABLE to disable all functional blocks. Set nviRequest to

0,RQ_ENABLE to enable all function blocks. Set nviRequest to 1,RQ_DISABLE to disable

only functional block 1.

The first value of nvoStatus is the functional block, and the 3rd bit in the bit array is 1 when

disabled.

*

NOTE: BLK = Function Block, VAR = Lon Network Variable, SNVT = Standard Network Variable Type