E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 59

Advertising
background image

DIN-MON™ SMART METER

59

62-0442—04

41061

2

Float

Voltage, line phase B to N

Volts-N

R

41063

2

Float

Voltage, line phase C to N

Volts-N

R

41065

2

Float

Voltage, line phase A to B

Volts-L

R

41067

2

Float

Voltage, line phase B to C

Volts-L

R

41069

2

Float

Voltage, line phase C to A

Volts-L

R

41071

2

Float

Phase angle, phase A

Degree

R

41073

2

Float

Phase angle, phase B

Degree

R

41075

2

Float

Phase angle, phase C

Degree

R

44001

3

6

Custom

Interval Day Block

R/W

44007

4

1*

Integer

Interval Data (1 register per

interval)

Pulse

R

45501

5

2*

Custom

Interval Data Headers (2

registers per day)

R

46025

6

8

Custom

RTC Date/Time

R/W

46049

7

8

Custom

EZ7 ID, Modbus ID, Serial

R/W

46057

8

Custom

Recorder Info., Demand

Interval

R/W

46513

8

Custom

Flags L1: Power Failure,

Battery

R

46521

8

Custom

Flags L2: Power Failure Date

R

1. To clear single meter kWh/kVARh, set multiple points at 40001 or 41001 for 8 points

with data set to 0000 0000 0000 0000 0000 0000 0000 0000. Jumper J6 must be closed.
2. N/A
3. To set the interval data day block, set multiple points at 44001 for 6 points with data set

to 0C0I 0000 MMDD YYYY 0000 0000. 0C = Channel, 0I = Interval (0F = 15 minute inter-

vals, 05 = 5 minute intervals).

4. Each register represents a 15 or 5 minute kWh pulse value based on the interval day
block. 96 registers max with 15 minute intervals. 288 registers max with 5 minute
intervals. The first interval data register 44007 represents the pulse count for the first

15 or 5 minute interval beginning at midnight.
5. The interval data headers represent days with available interval data. Each day repre-

sents 2 registers. Format: MMDD YYYY.

6. To set the date and time, set multiple points at 46025 for 4 points with data set to

HHMM SSDW MMDD YYYY (DW= day of week).

7. To change the ModBus ID, set single point at 46050 with data set to new ModBus

ID (e.g. 1 to 247). Jumper J6 must be closed.

ADDRESS REG

TYPE

DESCRIPTION

UNITS

R/W