DIN-MON™ SMART METER

55

62-0442—04

11.0 FREQUENTLY ASKED QUESTIONS

Q. When providing line voltage to the meter, can I tap off from the same breaker I

am monitoring?

A. Yes, the voltage can be pulled from the same breaker being monitored.

Q. Can the meter’s line voltage wires be run in the same conduit as the sensor

leads?

A. Yes. There will be no effect if the sensor leads and line voltage wires are run in the

same conduit.

Q. Can the meter’s communication wires and line voltage be run in the same

conduit?

A. It is not recommended to run these wires together due to noise concerns and their

effects on the communications signal integrity. Communications wires can be

routed separately using a 3/4” conduit port.

Q. How do I find the cost for kWh and kW to bill my tenants?

A. Your local utility bill should list the cost per kWh and kW. If not, simply call your

utility and ask them to provide you with the cost per kWh and kW.

Q. What size wire do I use for the line voltage leads?

A. These wires are normally sized at #14 AWG, but be sure to confirm this

requirement with your local and national electrical code requirements.

Q. What size wire should I use to extend the current sensor leads?

A. These wires are normally 14-22 AWG, twisted-pair arrangement. Consult your

electrical code for proper wiring requirements.