5.0 COMMUNICATION PROTOCOLS

The Din-Mon™ meter supports multiple communication protocols. Refer to section 2.1

Ordering Information to check your meter model configuration to determine which

protocol(s) it supports.

• Refer to section “Wiring the Communications” for wiring details.

• Refer to section “Setting Communication Protocol” for selecting available protocols.

If the protocol you need is not listed in the menu selection, verify the model number

you ordered.

• Refer to the Appendices for Modbus point maps, BACnet objects, and LonWorks

SNVTs.

5.1.1 Modbus RTU

The Din-Mon™ Modbus RTU meter communicates with building automation

equipment over a 3-wire (3-conductor) RS-485 network using Modbus RTU protocol.

The meter is shipped with a Modbus ID number of 1. The Modbus ID range is 1 to 247.

There can be no duplicate numbers on a RS-485 network, so caution must be taken

when assigning a meter ID number prior to its installation on the network.

5.1.2 BACnet MS/TP

The Din-Mon™ BACnet MS/TP meter communicates with building automation

equipment over RS-485 network using BACnet MS/TP protocol.

The meter is shipped with a BACnet instance device ID number of 1 and MS/TP MAC

of 1; both of these numbers must be unique within an MS/TP network.

The meter MS/TP MAC can be numbered from 0 to 127; the MAX Master range is 1 to

127; the BACnet instance device ID range is 0 to 4194303.

5.1.3 Baud Rate and Settings on RS-485

RS-485 communication can operate at different baud rates (speed). The baud rate is

selected via the LCD display menu. There are 4 baud rate selections: 9600 (factory

default), 19200, 38400, and 76800 baud; higher baud rates would require shorter

cable length. The setting is 8-parity bits, no-parity, 1-stop bit.