5 lonworks wiring (optional on d5 models only) – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 32

Advertising
background image

DIN-MON™ SMART METER

62-0442—04

32

4.8.5 LonWorks Wiring (Optional on D5 Models Only)

LonWorks communication connections are provided through a 2-position screw

terminal plug on top of the meter. This port can be connected to a LonWorks TP/FT-10

(Twisted Pair / Free Topology) network using 24 AWG twisted pair cable, TIA 568A

Category 5 or equivalent.

Fig. 26. 2-Position Screw Terminal Plug and Service Pin.

WIRING THE CONNECTION

1. Remove the communications terminal cover.

2. Remove the 2-position screw terminal plug from the meter.

3. Connect each conductor of network cable to each screw termi-

nal. Torque screws to 2 in-lbs.

(NOTE: Connection is polarity independent.)

4. Re-install the 2-position screw terminal plug to the meter.

COMMISSIONING LONWORKS NODE

1. With all TP/FT-10 network connections made, apply power to the meter. Allow

ample startup time.

2. The network configuration tool using the TP/FT-10 standard can be set to search

for a Neuron ID or listen for a Neuron ID when the service pin is pressed.

a.

Neuron ID: The Neuron ID is printed on the Order Specification label located

on the side of the meter enclosure. Enter the Neuron ID into the network

configuration tool and discover the node on the network.

b.

Service Pin: Set the network configuration tool to detect ServicePin. Press

the Service Pin switch located next to the 2-position screw terminal plug.

Refer to figure above.

3. Once commissioning has been completed, replace the communications terminal

cover, and fasten with screw provided.

Refer to Communication Protocols Section for details on LonWorks TP/FT-10.

M35115

SERVICE PIN

2-POSITION SCREW

TERMINAL PLUG

LON TERMINAL

M35116

Advertising