2 configurable settings from the display menu – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 41

Advertising
background image

DIN-MON™ SMART METER

41

62-0442—04

7.2 Configurable Settings from the Display Menu

Item

Main Menu

Sub Menu

Range

Default

1

Date &Time

Date

MM-DD-YYYY

00-00-0000

Time

HH:MM:SS

00:00:00

2

Device ID

EZ7 ID

1A..8Z

1A

Modbus ID

1..247

2

BACnet ID

0..1\4194303

1

3

IP Settings

Enable DHCP?

Y or N

N

IP Address

255.255.255.255 192.168.0.1
255.255.255.255 255.255.255.0
255.255.255.255 192.168.0.1

4

Register to BBMD

BBMD IP Address

255.255.255.255

BBMD Port

0-65535

Live-Time

0-65535

0

5

BACnet Settings

MS/TP MAC

0..127

1

MAX Master

1..127

127

Port

47808

6

Pulse Value

Out Channel

1 or 2

1

Use Default

Y or N

Y

WHr/P

(meter

amperage)

7

Protocol

RS-485

Modbus, MS/TP,

EZ7

Ethernet

8

Baud Rate

RS-485 comm.

speed

9600, 19200,

38400, or 76800

9600

9

Phase Loss

Phase Loss / VAR-

hour

Phase Loss or

VAR-Hour pulse

Phase Loss

10

CT Selection

CT Type

Split or Solid

CT Size

Default,

Unknown, 25-800

11

Access Protect

Remote access

protect?

Y or N

N

LCD access protect? Y or N

N

12

Change Password

Old password

0000-9999

N

New password

0000-9999

Confirm

Y or N

13

Reset KW/KWH

Reset kW Only?

Y or N

N

Reset All?

Y or N

N

14

Exit

Return to normal

display mode.