7.2.3 Setting Device ID (BACnet)

To change the Device ID, complete the following steps:

1. Press MENU button.

2. Use UP or DOWN button until the arrow is on the

DEVICE ID line.

3. Press SELECT button.

4. Use UP or DOWN button to make changes.

5. Press SELECT button to advance to the next setting. Repeat this step until all

the Device ID settings have been updated.

6. Press MENU to complete the changes. If changes were made, you’ll be asked to

save changes.

7. Press UP or DOWN to select ‘Y’ or ‘N’.

8. Press SELECT button to accept the selection. This will return you to the main

menu.

9. Select EXIT to get out of programming mode and return to normal display mode.

FIELD RANGE: EZ7 ID=[1A..1Z]..[8A..8Z]; BACnet ID=[0..4194303]

7.2.4 Setting Ethernet IP Address

To change the Ethernet IP Address, complete the following

steps:

1. Press MENU button.

2. Use UP or DOWN button until the arrow is on the IP

SETTINGS line.

3. Press SELECT button.

4. Use UP or DOWN button to make changes.

To change by digit, refer to note in Section 7.1 Navigating Menus.

5. Press SELECT button to advance to the next setting. Repeat this step until all

the IP address settings have been updated.

6. Press MENU to complete the changes. If changes were made, you’ll be asked to

save changes.

7. Press UP or DOWN to select ‘Y’ or ‘N’.

8. Press SELECT button to accept the selection. This will return you to the main

menu.

9. Select EXIT to get out of programming mode and return to normal display mode.

FIELD RANGE: IP, Mask, Gateway=[000.000.000.000 – 255.255.255.255]

DEVICE ID

EZ7

1A

BACNET

2

ENABLE DHCP? N

I192.168.0.168

M255.255.255.0

G192.168.0.1