4 modbus tcp/ip, 5 bacnet ip, 6 lonworks tp/ft-10 – E-Mon E-D5-600800-S*SPL3-V3KIT3 User Manual

Page 35

Advertising
background image

DIN-MON™ SMART METER

35

62-0442—04

5.1.4 Modbus TCP/IP

The Din-Mon™ D5 Modbus TCP/IP meter communicates with building automation

equipment over an Ethernet communication on port 502. The default IP address is

192.168.0.168, unless specified in the order form.

The meter is shipped with a Modbus ID number of 1. The Modbus ID range is 1 to 247.

5.1.5 BACnet IP

The Din-Mon™ D5 BACnet IP meter communicates with building automation

equipment over an Ethernet communication on port 47808.

The meter is shipped with a BACnet instance device ID number of 1. The BACnet

instance device ID range is 0 to 4194303.

5.1.6 LonWorks TP/FT-10

The Din-Mon™ D5 LonWorks meter communicates with building automation

equipment via a TP/FT-10 (Twisted Pair - Free Topology) network. End users can read

meter point data via SNVTs (Standard Network Variable Types).

The meter is shipped configured. If the network is already configured, the LonWorks

meter will need to be recommissioned.

5.1.7 EZ7 on RS-485 and Ethernet

All Din-Mon™ meters have EZ7 protocol on RS-485 and Ethernet built-in for

communicating with E-Mon Energy software. EZ7 is an E-Mon proprietary protocol.

The meter is shipped with a default EZ7 ID of 1A. The EZ7 ID range is 1A..1Z to

8A..8Z.