6.0 EXTERNAL INTERFACE

The Din-Mon™ meter has 2 pairs of output terminals.

1. Watt-Hour pulse output.

2. VAR-Hour pulse or Phase Loss output.

6.1 Pulse Output

The board contains two pulse outputs for use by Building

Automation Systems, etc. One pulse is in watt-hours, the second

pulse is in VAR-hours. They are polarity independent. The

maximum current allowed is 400 mA and the maximum voltage

allowed is 40 VAC or VDC. See the table below for maximum pulse

rate.

Table 1. Pulse Rate Maximum Load.

Index

Voltage Rating

Maximum pulse rate per

minute (at rated load)

0

Others

User

1

120/208 (3

Ш

)

307.52

2

277/480 (3

Ш

)

708.00

3

346/600 (3

Ш

)

886.88

4

120/208 (2

Ш

)

204.96

5

277/480 (2

Ш

)

472.96

6

346/600 (2

Ш

)

591.20

7

120 (1

Ш

)

102.40

8

277 (1

Ш

)

236.48

OUTPUT TERM

M35119

M35120

INTERNAL CIRCUIT